Foam Bladder Tank for Fire Fighting System

Model NO.: PHYM
Trademark: GAN
Origin: Shenzhen, China
HS Code: 8424100000
Model NO.: PHYM
Trademark: GAN
Origin: Shenzhen, China
HS Code: 8424100000
Data Sheet of Foam Bladder Tank
 
INTRODUCTION
The foam bladder tank is the main unit of the foam extinguishing system. The foam tank and the low/medium expansion foam generator construct the low/medium foam spraying system. It can also construct the high expansion total flooding extinguishing system with high expansion foam generator. It aims at fire of class A and class B, especially for fire of class B. The foam bladder tank mainly applied in occasions such as places where inflammable liquid was produced, stored and transported. It is especially suitable to put out fire caused by inflammable liquid tank or large scale of spill fire.

Foam Bladder Tank for Fire Fighting System



PRINCIPLE
The device consists of pressure tank, bladder, proportioner, pressure gauge, valves and pipeline. A pump is needed to supply pressurized water. When pressurized water flow though proportioner, a small part of water (3%-6%) flow into tank from branch pipe to press the bladder to swap out equal foam concentrate and then mix with another part of water (97%-93%) to form foam solution in proportioner and provide to foam generator.

PARAMETERS
Proportioner
Model No.
PHY4 PHY8 PHY16 PHY24 PHY32 PHY40 PHY64 PHY72
Diameter (DN) 50 65 80 100 100 150 150 150
Mixing Ratio 3% or 6%
Rated Working Pressure (MPa) 1.2
Working Pressure Range (MPa) 0.3~1.2
Rated Flow (L/S) 4 8 16 24 32 40 64 72
Flow Rang (L/S) 1~4 2~8 3~16 4~24 8~32 12~40 15~64 17~72
Pressure Drop (MPa) ≤0.2
 
INSTALLATION
Device should be installed at places with shelter to avoid sun and rain. Ambient temperature should be within 40°C and leave enough space for operation. Device should be installed at concrete floor and fastened with anchor nuts.
Do the hydraulic test after installing. Open the tank vent valve first then fill water into bladder from concentrate draining pipe. Then close tank vent valve when bladder is full of water. Pressurize the system and keeping for 10 minutes when pressure gets test pressure, tank should have no leakage. Close water inlet valve and open water drainage valve and concentrate drainage valve to drain water away in tank and bladder. (We will do this test when products leave the factory)

 
Horizontal Bladder Tank
Foam Bladder Tank for Fire Fighting System
1. Tank   2. Pressure Gauge   3. Water Inlet Pipe   4.Feed Inlet   5. Concentrate Outlet   6. Safety Valve
7. Tank Vent Pipe   8. Inspection Hole   9. Lifting Lug  10. Check Valve   11. Bladder Vent
12. Liquid Indicator   13. Bracket   14. Water Drainage   15. Foam Drainage   16. Proportioner

 
CAPACITY LITERS D
mm
L
mm
L1
mm
L2
mm
B
mm
B1
mm
B2
mm
H
mm
H1
mm
WEIGHT
(KG)
500 800 1450 630 480 1250 705 400 1400 700 280
1000 1000 1800 800 625 1350 760 330 1600 800 350
1500 1000 2350 1270 1120 1350 760 340 1650 810 450
2000 1200 2300 1230 1025 1550 1000 390 1800 900 550
2500 1200 2650 1550 1350 1550 1000 400 1850 910 700
3000 1400 2500 1320 1120 1750 1200 400 2100 1000 800
3500 1400 2800 1450 1250 1750 1200 400 2100 1000 950
4000 1500 2750 1500 1300 1850 1300 500 2200 1100 1050
5000 1600 3100 1800 1500 1950 1400 850 2300 1100 1200
5500 1600 3250 1800 1500 1950 1400 850 2300 1100 1300
6000 1600 3400 1900 1700 1950 1400 850 2300 1200 1400
7500 1800 3500 2100 1800 2200 1800 850 2500 1200 1600
9000 2000 3500 2000 1800 2400 1800 1350 2700 1300 1900
10000 2000 3850 2000 1800 2400 1800 1350 2700 1300 2200
11000 2000 4100 2000 1800 2400 1800 1350 2700 1300 2600
13000 2200 4000 2350 2000 2600 2000 1400 2900 1400 3000
15000 2300 4300 2350 2000 2700 2000 1400 3000 1460 3500
Size and weight are just for reference, real products can be different.
 
Vertical Bladder Tank
Foam Bladder Tank for Fire Fighting System
1. Tank   2. Pressure Gauge   3. Water Inlet Pipe   4.Feed Inlet   5. Concentrate Outlet   6. Safety Valve
7. Tank Vent   8. Inspection Hole   9. Lifting Lug  10. Check Valve  11. Bladder Vent
12. Liquid Indicator   13. Bracket   14. Water Drainage Valve  15. Foam Drainage   16. Proportioner